Environment Monitoring System IP Temp CAT5 Video Extender HDMI VGA DVI KVM Switch, Video Splitter, Video Matrix Switch
E-ACLM-P12-V2
E-ACLM-P12-V2

AC Power Monitor with Relay

NTI Part #: E-ACLM-P12-V2
Environment Monitoring System AC & DC Power Monitors
Power Relays & Sensors compatible with ENVIROMUX® E-2D, E-5D and E-16D

Overview

  • Reports AC Voltage, Frequency, Power, and Current.
    • Monitors Power from one AC inlet to one AC outlet, between 50~250VAC and 47~63Hz.
    • Monitors the number of swells, sags, and spikes.
      • Monitors swell and sag duration of 0.1 second to 1 minute.
  • Includes Relay with configurable disconnect settings: threshold reboot, or manual reboot.
  • Accuracy
    • Voltage accuracy: ±1% FS at 32 to 104°F (0 to 40°C).
    • Frequency accuracy: ± 1%
    • Current accuracy: ± 2.7%
  • Outlet Max load rating (continuous):
    • E-ACLM-P18-V2 (US/Canada): 18A rated load, 20A maximum.
    • E-ACLM-P12-V2 (US/Canada): 12A rated load, 15A maximum.
    • E-ACLM-P8-V2 (Euro/UK): 8A rated load, 10A maximum.
  • Capable of measuring current surges from 300 mA to 20A.
  • User defined minimum and maximum voltage and power thresholds.
  • Capable of detecting user selected spike events with a peak greater than 50V, 250V, 500V, or 1KV.
  • Cables included:
    • E-ACLM-P12/8-V2: one country-specific IEC 320 C13 line cord, and one IEC 320 C14 to IEC 320 C13 cord set for connection to AC load.
    • E-ACLM-P18-V2: one L6-20r to IEC 320 C20, and one L6-20p to IEC 320 C19.
  • Supports CAT5/5e/6 cable up to 1,000 ft. (305 m).
    • E-2D/5D: supports CAT5/5e/6 cable up to 750 ft (229 m).
  • Dimensions (WxDxH) in:
    • E-ACLM-P12/8-V2: 7.0x5.5x1.65 (178x140x42 mm).
    • E-ACLM-P18-V2: 7.0x6.5x1.65 (178x165x42 mm).
  • Weight: 1.6 lbs (726 g).
  • Current consumption: 13mA @ 5VDC, 125mA @ 12VDC.
  • Powered by E-2D/5D/16D.
  • Operating temperature: 32 to 104°F (0 to 40°C)
  • Regulatory approvals: CE, RoHS
  • Compatible with E-FSC Fiber Converter/Extender.
    • Use to extend sensor up to 1.2 miles (2 km) from the ENVIROMUX unit.